Tabela 1 PR211 tipo |
S. N° |
Função |
Definições |
Digite |
PR211 |
PR211 |
PR211 |
PR211 |
Reinicialização Factroy |
Os polacos |
3P |
3P |
3P |
3P |
Classificação (UMA) |
250 |
400 |
800 |
1600 |
1 |
L |
Corrente de sobrecarga (UMA) |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1, 0)xIn |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1, 0)xIn |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1, 0)xIn |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1, 0)xIn |
1.0In |
2 |
Tempo de Retardo em sobrecarga Configuração Atual |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S |
3 |
I |
Instantâneos a configuração atual |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
10Em |
Tabela2 PR212 tipo |
S. N° |
Função |
Definições |
Digite |
PR212 |
PR212 |
PR212 |
PR212 |
Reinicialização Factroy |
Os polacos |
3P |
3P |
3P |
3P |
Classificação (UMA) |
250 |
400/630 |
800 |
1600 |
1 |
L |
Corrente de sobrecarga (UMA) |
(0.4, 0.5, 0.55, 0, 6, 0.65, 0.7, 0.75, 0, 8)xIn |
(0.4, 0.5, 0.55, 0, 6, 0.65, 0.7, 0.75, 0, 8)xIn |
(0.4, 0.5, 0.55, 0, 6, 0.65, 0.7, 0.75, 0, 8)xIn |
(0.4, 0.5, 0.55, 0, 6, 0.65, 0.7, 0.75, 0, 8)xIn |
1.0In |
2 |
Tempo de Retardo em sobrecarga Configuração Atual |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S |
3 |
S |
Curto circuito - Configuração atual (A) |
(1, 2, 3, 4, 6, 8, 10, OFF)xIn |
(1, 2, 3, 4, 6, 8, 10, OFF)xIn |
(1, 2, 3, 4, 6, 8, 10, OFF)xIn |
(1, 2, 3, 4, 6, 8, 10, OFF)xIn |
6Em |
4 |
Tempo de retardo no curto-circuito Configuração Atual |
0, 05, 0, 1, 0, 25, 0, 5 |
0, 05, 0, 1, 0, 25, 0, 5 |
0, 05, 0, 1, 0, 25, 0, 5 |
0, 05, 0, 1, 0, 25, 0, 5 |
0, 1S |
5 |
I |
Instantâneos a configuração atual |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1, 5, 2, 4, 6, 8, 10, 12, OFF)xIn |
10Em |
6 |
G |
Falha no Ajuste Atual (A) |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, OFF)xIn |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, OFF)xIn |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, OFF)xIn |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, OFF)xIn |
1.0In |
7 |
Tempo de retardo no solo a definição de falha |
0, 1, 0, 2, 0, 4, 0, 8 |
0, 1, 0, 2, 0, 4, 0, 8 |
0, 1, 0, 2, 0, 4, 0, 8 |
0, 1, 0, 2, 0, 4, 0, 8 |
0.4S |
8 |
|
Selecção de eléctrico ou electrónico conjunto de parâmetros |
Conjunto de funções (interruptor ELT/MAN) |
9 |
|
Usado para configurar parâmetros do interruptor dip da linha zero |
InN=%no interruptor, 50/100 |
10 |
|
Tomada para a ligação do dispositivo de medição |
Soquete do painel |