Tabela 1 PR211 tipo |
S.n° |
Função |
Definições |
Digite |
PR211 |
PR211 |
PR211 |
PR211 |
Reinicialização Factroy |
Os polacos |
3P |
3P |
3P |
3P |
Classificação (UMA) |
250 |
400 |
800 |
1600 |
1 |
L |
Ajuste da Corrente de sobrecarga (A) |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1,0)xIn |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1,0)xIn |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1,0)xIn |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1,0)xIn |
1.0In |
2 |
Tempo de retardo na configuração atual de sobrecarga |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S |
3 |
I |
Ajuste da Corrente instantânea |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
10Em |
Tabela2 PR212 tipo |
S.n° |
Função |
Definições |
Digite |
PR212 |
PR212 |
PR212 |
PR212 |
Reinicialização Factroy |
Os polacos |
3P |
3P |
3P |
3P |
Classificação (UMA) |
250 |
400/630 |
800 |
1600 |
1 |
L |
Ajuste da Corrente de sobrecarga (A) |
(0.4,0.5,0.55,0,6,0.65,0.7,0.75,0,8)xIn |
(0.4,0.5,0.55,0,6,0.65,0.7,0.75,0,8)xIn |
(0.4,0.5,0.55,0,6,0.65,0.7,0.75,0,8)xIn |
(0.4,0.5,0.55,0,6,0.65,0.7,0.75,0,8)xIn |
1.0In |
2 |
Tempo de retardo na configuração atual de sobrecarga |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S |
3 |
S |
Curto circuito - Configuração atual (A) |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
6Em |
4 |
Tempo de retardo no ajuste da corrente de curto-circuito |
0,05, 0,1, 0,25, 0,5 |
0,05, 0,1, 0,25, 0,5 |
0,05, 0,1, 0,25, 0,5 |
0,05, 0,1, 0,25, 0,5 |
0,1S |
5 |
I |
Ajuste da Corrente instantânea |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
(1,5, 2, 4, 6, 8, 10, 12, OFF)xIn |
10Em |
6 |
G |
Ajuste da Corrente de falha de aterramento (A) |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
1.0In |
7 |
Tempo de retardo na definição de falha de aterramento |
0,1, 0,2, 0,4, 0,8 |
0,1, 0,2, 0,4, 0,8 |
0,1, 0,2, 0,4, 0,8 |
0,1, 0,2, 0,4, 0,8 |
0.4S |
8 |
|
Selecção de parâmetros eléctricos ou electrónicos |
Conjunto de funções (interruptor ELT/MAN) |
9 |
|
Usado para configurar parâmetros do interruptor dip da linha zero |
InN=%no interruptor,50/100 |
10 |
|
Tomada para a ligação do dispositivo de medição |
Soquete do painel |